| Plan Review Notes For Permit 05040903 |
| Permit Number |
05040903 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2006-02-09 00:00:00 | ** REDLINED ** | | | | | | VERIFY OCP FOR CU, SHOWS 9.8KW, 40A OCP | | | | | | MIN 8' GROUND ROD REQUIRED PER 250.52A | | | | | | VERIFY MIN OCP FOR AHU#2, PER 424.3B, | | | MIN OCP 125%. |
|