| Plan Review Notes For Permit 05040901 |
| Permit Number |
05040901 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-06-30 00:00:00 | BUILDING REVIEW PROVISO: | | | 1- SHUTTERS UNDER A SEPARATE PERMIT. | | | 2- NEED REVISED ENERGY CALCULATIONS FOR | | | WORST CASE SCENARIO. | | | 3- REVISE DOOR/WINDOW SCHEDULE TO MATCH | | | PLANS. INCLUDING SYMBOL USED. | | | 4- DETAIL 5/D1: CONNECTOR HTS20 CAN'T | | | SUPPORT BEAM. REVISE AS REQUIRED. SEC. | | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | | 5- TRUSS ANCHOR SCHEDULE: UPDATE NAIL | | | SIZE USED FOR HUS26. SEE CATALOGUE. | | | 6- ROOF FRAMING PLAN: REVISE CONNECTOR | | | SPECIFIED AT ENTRY PORCH TO MATCH | | | DETAILS 5 & 6 OF DRAWING D-1. | | | 7- PROVIDE PRODUCT APPROVAL FOR: | | | A) 9'-0" WIDE SLIDING GLASS DOORS. | | | B) 8'-0" HIGH ENTRY DOORS. | | | 8- SHEET A-5 SHEAR VALUE NOTE: | | | A) PROVIDE HAND CALCULATIONS. SEC. | | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | | B) WHY USING TIMBER MANUAL TO CALCULATE | | | TAPCON VALUES?. | | | C) SPECIFY TIMBER MANUAL EDITION. |
|