| 2005-04-26 00:00:00 | ********** UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SEE PANEL "A" SHOWS FEED |
| | TO PANEL "B" AS 100A OCP ON #6 AWG. |
| | PLEASE SEE 240.4,310.16 AND PLEASE |
| | CORRELATE WITH RISER DIAGRAM. |
| | PLEASE ALSO SEE THIS IS SHOWN AS 100A SP |
| | BRKR ON ONE PHASE? (MISPRINT) |
| | |
| | 2)NOTE: PLEASE SEE PANEL "B" SHOWS SUB |
| | PANEL "C" IN TWO DIFFERENT LOCATIONS? |
| | PLEASE SEE THIS IS SHOWN ON SAME PHASE. |
| | PLEASE ALSO CORRELATE AWG FOR 60A OCP. |
| | SHOWS #6 AND #8? |
| | PLEASE ALSO SEE SINGLE POLE 60A FOR |
| | ADDITIONAL SUB PANEL. |
| | PLEASE SEE 240.4,310.16, 310.15B6 |
| | |
| | 3)NOTE: PLEASE SEE NOTE ADDED TO CENTER |
| | OF PLANS WHICH IS A PROVISO SET UP BY A |
| | PLAN REVIEWER FOR A PREVIOUS PROJECT. |
| | THIS COMMENT FROM OTHER ELECTRICAL PLAN |
| | REVIEW SHOULD NOT BE LOCATED ON THESE |
| | PLANS. |
| | PLEASE REMOVE. |
| | |
| | 4)NOTE;PLEASE SEE MISSING RECEPT(S) PER |
| | 210.52 C1, 210.8A6 |
| | |
| | 5)NOTE: PLEASE SEE ONE OF THE ABOVE |
| | CIRCUITS FOR SD'S (#38) IS THE SAME |
| | CIRCUIT ON PANEL SCHEDULE FOR SUB PANEL |
| | "B". |
| | |
| | 6)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS |
| | ON PLANS. |
| | 215.5 |
| | |
| | 7)NOTE: PLEASE SHOW LOADS ON EACH |
| | ELECTRICAL PANEL. PANEL "B AND "C |
| | MENTIONS TO SEE LOAD CALCS, HOWEVER |
| | THESE PANELS NEED TO SHOW ACTUAL LOAD |
| | FOR THOSE PANELS. |
| | 220,215.5 |
| | |
| | 8 )NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | 9)NOTE: PLEASE SEE PLANS REFERENCE 1999 |
| | NEC FOR 210.12. WE HAVE BEEN UNDER THE |
| | 2002 NEC SINCE JULY 1ST, 2003 |
| | |
| | 10)NOTE: PLEASE SEE SD'S ON MULTIPLE |
| | CIRCUITS WHEN THEY ARE REQUIRED TO BE |
| | WIRED "INLINE". PLEASE SEE #38 AND 25. |
| | |
| | PLEASE BE SURE TO REMOVE ALL OLD VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. |
| | PLEASE SEE ONE COPY/SET OF OLD SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |