| 2005-05-23 00:00:00 | DENIED |
| | |
| | 1)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) THE COUNY PROPERTY APPRAISER'S |
| | RECORDS INDICATE A DIFFERENT OWNER THAN |
| | LISTED ON THE PERMIT APPLICATION.SUBMIT |
| | A COPY OF THE WARRANTY DEED SHOWING THE |
| | NEW OWNER OF RECORD. |
| | |
| | 3) THE USP JL210 AND HD212 ARE WOOD TO |
| | WOOD HANGERS AND ARE NOT DESIGNED OR |
| | TESTED TO BE USED WITH TAPCONS. SPECIFY |
| | AN APPROPRIATE MASONRY HANGER. |
| | |
| | 4) SUBMIT THE COVERSHEET WITH THE FL# |
| | FOR THE METAL ROOF PANELS. |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. |
| | |
| | 5) SUBMIT THE COMPLETE TESTING |
| | INFORMATION FOR THE PLASTRO/NANYA |
| | GLAZED DOORS, SHOWING THAT THEY ARE |
| | IMPACT RESISTANT AND ARE NOT REQUIRED TO |
| | BE SHUTTERED (SEE STORM PANEL SCHEDULE). |
| | SUBMIT THE INSTALLATION DRAWINGS FOR THE |
| | DOORS THAT WILL BE INSTALLED FROM THE |
| | ONES LISTED ON THE STATE WEBSITE. |
| | |