| 2005-05-23 00:00:00 | DENIED |
| | |
| | 1)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) THE OWNER OF RECORD FOR THE PROPERTY |
| | ON THE PERMIT APPLICATION DOES NOT MATCH |
| | THE COUNTY PROPERTY APPRAISER'S RECORDS. |
| | SUBMIT A COPY OF THE WARRANTY DEED WITH |
| | NEW OWNER. |
| | |
| | 3) THE USP JL28 AND JL210 HANGERS |
| | SPECIFIED ON SHEET 5B ARE NOT DESIGNED |
| | OR TESTED TO BE USED WITH TAPCONS. |
| | SPECIFY AN APPROPRIATE MASONRY HANGER. |
| | |
| | 4) SUBMIT THE STATE COVERSHEET WITH THE |
| | FL# FOR THE METAL ROOF PANELS. |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. |
| | |
| | 5) SUBMIT THE TEST REPORTS FOR THE |
| | PLASTRO/NANYA GLAZED DOORS, INCLUDING |
| | LARGE MISSLE IMPACT TESTING. SUBMIT THE |
| | INSTALLATION DRAWINGS FROM THE FLORIDA |
| | PRODUCT APPROVAL WEBSITE FOR THE DOORS |
| | THAT WILL BE USED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |
| | |
| | |
| | |