| Plan Review Notes For Permit 05040750 |
| Permit Number |
05040750 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-05-03 00:00:00 | ALL BEDROOMS SHALL BE ARC FAULT | | | PROTECTEDJL | | 2005-04-21 00:00:00 | NEED DRAWINGS SHOWING OUTLETS AND | | | SWITCHES LOCATIONS, AND ALSO FIXTURES. | | | | | | ALL EXISTING BOXES AND RACEWAYS TO BE | | | SUPPORTED. | | | | | | ALL BATH OUTLETS TO BE GFCI PROTECTED. | | | | | | ALL KITCHEN COUNTER TOP OUTLETS TO BE | | | GFCI PROTECTED. | | | | | | BEDROOMS SHALL HAVE SMOKE DETECTORS | | | INSTALLED INSIDE AND OUT. | | | | | | QUESTIONS CALL JAKE LEAHY 644-7291 OR | | | DAN KEMPA 805-6745 |
|