| Plan Review Notes For Permit 05040742 |
| Permit Number |
05040742 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-05-02 00:00:00 | DENIED | | | REFERENCE; FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT A1 SANITARY RISER DIAGRAM DOES | | | NOT MEET CODE REQUIREMENTS: | | | A. TRAP REQUIRED FOR SHOWER SEC 1002.1 | | | B. SHOW ALL PIPE SIZES TABLE 710.1(1) | | | C. WASH MACHINE TRAP SHALL CONNECT LOW | | | ON THE STACK FOR STANDPIPE. SECTION | | | 1002.1 (SEE RED LINE CORRECTIONS ON ONE | | | SET OF PLANS). | | | 2) INFORMATIONAL THE CLEANOUT OPPOSITE | | | OF THE W/C IS NOT REQUIRED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|