| 2005-04-25 00:00:00 | ******* UNSAT ********** |
| | |
| | 1)NOTE: PLEASE SEE NOE ELECTRICAL PLANS |
| | FOR PROPOSED WORK WAS SUBMITTED, HOWEVER |
| | AND ELECTRICAL PERMIT IS BEING |
| | REQUESTED. |
| | PLEASE SUBMIT ELECTRICAL DETAILS FOR |
| | ELECTRICAL WORK BEING APPLIED FOR. |
| | PLEASE SUBMIT SIGNED, SEALED PLANS BY A |
| | FL REG PE. FS 471.003. |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE SEE FS 481.229 WHICH |
| | REQUIRES PLANS TO BE SIGNED, DATED AND |
| | SEALED FOR WORK OVER $25K FOR COMMERCIAL |
| | BLDG. |
| | PLEASE ALSO SEE PLANS WHICH CONTAIN A |
| | TITLE BLOCK FOR AN ARCHITECTUAL FIRM ARE |
| | REQUIRED TO BE SIGNED, DATED AND SEALED |
| | BY SAID FIRM. |
| | TITLE BLOCK SHALL CONTAIN ALL |
| | INFORMATION AS SET-FORTH IN FAC |
| | 61G1-16.004 , FS 481.219, 481.221 |
| | PLEASE ALSO SEE ANY SHEETS BEING SIGNED |
| | AND SEALED, MUST CONTAIN A TITLE BLOCK |
| | AS STATED ABOVE. |
| | |
| | 3)NOTE: IF LIGHTNING PROTECTION SYSTEM |
| | IS GOING TO BE INSTALLED AND UNDER THE |
| | RESPONSIBLITY AND PERMIT OF ELECTRICAL |
| | CONTRACTOR SIGNED ON APPLICATION, THEN |
| | COMPLETE PLANS FOR INSTALLATIOON SHOWING |
| | ALL DETAILS AND INSTALLATION OF SYSTEM |
| | PER NFPA-780 SHALL BE SUBMITTED. |
| | IF LIGHTING PROTECTION SYSTEM WILL BE A |
| | SEPARATE PERMIT/PLANS, PLEASE REMOVE |
| | FROM APPLICATION AND FROM PROPOSED WORK |
| | ON DRAWINGS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |