| Plan Review Notes For Permit 05040709 |
| Permit Number |
05040709 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-08-04 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE ORIGINAL APPLICATION MUST BE | | | SUBMITTED WITH THE PLANS. | | | | | | 2} PLEASE VERIFY THE SCALE IS 1/8" AS | | | NOTED. | | | | | | 3} A RECEPTACLE NEEDS TO BE ADDED IN | | | BEDROOM #FOR COMPLIANCE WITH 210.52 | | | (A)(1). | | | | | | 4} THE #10 WIRE ON THE 60 AMP AHU | | | BREAKER IS IN VIOLATION OF 310.16. | | | | | | PLEASE HAVE MR. ESPINOZA SIGN HIS NAME | | | TO THE SEAL. IT APPEARS THIS SET IS | | | INITIALLED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|