Plan Review Notes
Plan Review Notes For Permit 05040709
Permit Number 05040709
Review Stop B
Sequence Number 2
Notes
Date Text
2005-08-08 00:00:00 
 DENIED
 COMMENT FROM FIRST REVIEW:
  
 4.BASED ON SBCCI BUILDING VALUATION
 DATA THE VALUE OF $47,000 IS TOO LOW.
 THE ROOM ADDITION ALONE IS
 451SQ.FT X $76.96 PER SQ.FT. = $34,700.
 PLUS THE COMPLETE RENOVATION OF THE
 EXISTING BUILDING INCLUDING A NEW SLAB
 ROOF FRAMING AND A COMPLETE INTERIOR
 DEMO AND REBUILD.
 RECALCULATE VALUE SUBMITTED AND PAY
 ADDTIONAL PERMIT FEES.
  
 NEW COMMENTS:
  
 A.EXISTING SLAB PERMIT 03040474 IS
 EXPIRED. NO FINAL INSPECTION IS SHOWN ON
 OUR RECORDS.
  
 B. FOOTING DESIGN SHALL BE A MINIMUM 16
 INCH FOOTING WITH 4" ABOVE GRADE AND 12
 INCHES BELOW GRADE AS MINIMUMS. FOOTING
 SHOW ON EXISTING PERMIT IS ONLY 12
 INCHES.FBC 1804.1.3
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER