2005-04-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB CODE
  
 1) SHT 6 SANITARY RISER DIAGRAM AND
 DRAIN PLAN DO NOT MEET CODE REQUIREMENTS
 FOR THE FOLLOWING:
 A. TUB NOT VENTED IN BATH #2 SECTION
 901.2.1.
 B. W/C IN BOTH BATHS SHALL NOT BE
 TRAPPED AS THERE IS AN INTEGRAL TRAP IN
 THE FIXTURE. SECTION 1002.1.
 C. LAVS IN BOTH BATHS TRAPS SHALL BE ON
 THE STACK NOT UNDERGROUND. SECTION
 1002.1.
 D. DRAIN PAN FOR THE WATER HEATER SHALL
 NOT CONNECT TO SANITARY, BUT SHALL DRAIN
 SEPARATELY OUTSIDE AND TERMINATE A
 MINIMUM OF 6" ABOVE GRADE, OR DRAIN TO
 AN INDIRECT WASTE RECEPTOR. SECTION
 504.8.2 - WATER HEATER PANS ARE NOT
 REQUIRED ON THE FIRST FLOOR. SECTION
 504.8.
 E. A/C CONDENSATE SHALL NOT DRAIN INTO
 THE SANITARY DRAINAGE SYSTEM, BUT SHALL
 DRAIN SEPARATELY TO THE OUTSIDE OF THE
 BUILDING MINIMUM 1 FOOT FROM THE
 STRUCTURE SIDEWALL. SECTION 1503.4.4 OF
 THE BUILDING CODE AND CITY CODE SECTION
 90-125(B).
 F. DRY HORIZONTAL VENT UPSTREAM OF THE
 W/C IN BATH #1 IS NOT APPROVED. SECTIONS
 905.3 & 905.4.
 2) SEE ATTACHED SHEET FOR AN EXAMPLE OF
 A SANT. RISER DIAGRAM THAT MEETS CODE
 REQUIREMENTS.
 3) ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS, AND LICENSE NUMBER
 ON EACH SHEET. THE ADDRESS AND LICENSE
 NUMBER ARE NOT WRITTEN ON EACH SHEET.
 FAC 61G15-25.002(2) & FS 471.025.
  
 REVIEW BY KEN STEVENS