| 2005-04-29 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 BUILDING |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | CITY WPB CODE |
| | |
| | 1) SHT 6 SANITARY RISER DIAGRAM AND |
| | DRAIN PLAN DO NOT MEET CODE REQUIREMENTS |
| | FOR THE FOLLOWING: |
| | A. TUB NOT VENTED IN BATH #2 SECTION |
| | 901.2.1. |
| | B. W/C IN BOTH BATHS SHALL NOT BE |
| | TRAPPED AS THERE IS AN INTEGRAL TRAP IN |
| | THE FIXTURE. SECTION 1002.1. |
| | C. LAVS IN BOTH BATHS TRAPS SHALL BE ON |
| | THE STACK NOT UNDERGROUND. SECTION |
| | 1002.1. |
| | D. DRAIN PAN FOR THE WATER HEATER SHALL |
| | NOT CONNECT TO SANITARY, BUT SHALL DRAIN |
| | SEPARATELY OUTSIDE AND TERMINATE A |
| | MINIMUM OF 6" ABOVE GRADE, OR DRAIN TO |
| | AN INDIRECT WASTE RECEPTOR. SECTION |
| | 504.8.2 - WATER HEATER PANS ARE NOT |
| | REQUIRED ON THE FIRST FLOOR. SECTION |
| | 504.8. |
| | E. A/C CONDENSATE SHALL NOT DRAIN INTO |
| | THE SANITARY DRAINAGE SYSTEM, BUT SHALL |
| | DRAIN SEPARATELY TO THE OUTSIDE OF THE |
| | BUILDING MINIMUM 1 FOOT FROM THE |
| | STRUCTURE SIDEWALL. SECTION 1503.4.4 OF |
| | THE BUILDING CODE AND CITY CODE SECTION |
| | 90-125(B). |
| | F. DRY HORIZONTAL VENT UPSTREAM OF THE |
| | W/C IN BATH #1 IS NOT APPROVED. SECTIONS |
| | 905.3 & 905.4. |
| | 2) SEE ATTACHED SHEET FOR AN EXAMPLE OF |
| | A SANT. RISER DIAGRAM THAT MEETS CODE |
| | REQUIREMENTS. |
| | 3) ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME, ADDRESS, AND LICENSE NUMBER |
| | ON EACH SHEET. THE ADDRESS AND LICENSE |
| | NUMBER ARE NOT WRITTEN ON EACH SHEET. |
| | FAC 61G15-25.002(2) & FS 471.025. |
| | |