| Plan Review Notes For Permit 05040646 |
| Permit Number |
05040646 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-05-05 00:00:00 | 1) PLEASE SUBMIT SPECS AND DETAILS | | | REGARDING THE FUEL TANK SUCH AS SIZE, | | | LOCATION, VENT PIPE ETC. | | | | | | 2) NFPA 704 MARKINGS ARE REQUIRED ON OR | | | IN THE VICINITY OF THE FUEL TANK. | | | | | | 3) IF MECHANICAL DAMAGE IS LIKELY, | | | PROTECTION OF THE FUEL TANK WILL BE | | | NECESSARY. | | | | | | 4) PLEASE PROVIDE FACTORY TEST CURVE | | | RESULTS FOR REVIEW. | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 835-2910 OR 805-6722 |
|