| Date |
Text |
| 2005-05-26 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FBC-2001 BUILDING |
| | |
| | 1) THERE SEEMS TO BE A CHANGE OF |
| | OCCUPANCY FROM RESIDENTIAL TO |
| | COMMERCIAL. IF THIS IS THE CASE, THE |
| | FOLLOWING WILL BE REQUIRED. |
| | A. SUBMIT A FLOOR PLAN SHOWING ALL |
| | EXISTING FIXTURES. SECTION 104.2.1. |
| | B. PLEASE INDICATE THE OCCUPANCY OF THE |
| | BUILDING. WHAT TYPE OF BUSINESS WILL BE |
| | IN THE BUILDING. |
| | C. FOR BUSINESS OCCUPANCY A DRINKING |
| | FOUNTAIN IS REQUIRED. TABLE 403.1 - |
| | SUBMIT A DETAIL SHOW COMPLIANCE WITH |
| | SECTIONS 11-4.15 & ALL SUBSECTIONS AS |
| | WELL AS 11-4.1.3(10)(A) PROVISIONS FOR |
| | THOSE WHO HAVE DIFFICULTY BENDING OR |
| | STOOPING. |
| | D. SUBMIT A DETAIL FOR TOILET/BATHROOM |
| | SHOWING COMPLIANCE WITH THE FOLLOWING |
| | SECTIONS. 11-4.16, 11-4.19, AND IF |
| | FIXTURES ARE PROVIDED 11-4.20 AND/OR |
| | 11-4.21 AND 11-4.22 WITH ALL |
| | SUBSECTIONS. |
| | E. IF A KITCHEN/BREAKROOM SINK IS |
| | PROVIDED, SUBMIT A DETAIL SHOWING |
| | COMPLIANCE WITH SECTION 11-4.24 AND ALL |
| | SUBSECTIONS. |
| | D. AN RPZ BACKFLOW IS REQUIRED ON THE |
| | WATER SERVICE TO THE BUILDING. |
| | |
| | INFORMATIONAL - ALL TRADES AND BUILDING |
| | SHALL BE BROUGHT UP TO CODE IF THERE IS |
| | A CHANGE OF OCCUPANCY. SEE SECTION 34 OF |
| | THE BUILDING CODE. MORE COMMENTS MAY BE |
| | FORTHCOMING WHEN PLANS ARE SUBMITTED. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |
| | |