| Plan Review Notes For Permit 05040598 |
| Permit Number |
05040598 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-05-05 00:00:00 | DENIED | | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT 2 PIPING SCHEMATIC DOES NOT | | | REFLECT THE POOL LAYOUT ON SHT 1. THE | | | POOL LAYOUT SHOWS SPA MAIN DRAINS, BUT | | | THE PIPING SCHEMATIC DOES NOT. SECTION | | | 104.2.1. | | | 2) FBC-2001 424.2.14.2 WATER RETENTION, | | | PROVIDE A POSITIVE MEANS OF RETAINING | | | WATER IN THE HEATER WHEN PUMP IS SHUT | | | OFF. MANUF. SPECIFICATION SHEET DOES NOT | | | SHOW POSITIVE MEANS OF RETAINING WATER | | | IN THE HEAT PUMP. PLEAS INDICATE AN | | | EXTERNAL HARTFORD LOOP TO SHOW | | | COMPLIANCE WITH THIS CODE SECTION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|