Plan Review Notes
Plan Review Notes For Permit 05040596
Permit Number 05040596
Review Stop P
Sequence Number 1
Notes
Date Text
2005-04-25 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
  
 1) SINKS IN CONFERENCE ROOM, 707, AND
 COFFEE STATION, 702, SHALL BE ACCESSIBLE
 PROVIDE THE FOLLOWING INFORMATION ON
 EACH DETAIL SHEET A-3.0:
 A. KNEE CLEARANCE 11-4.24.3
 B. SINK DEPTH 11-4.24.4
 C. CLEAR FLOOR SPACE 11-4.24.5, FORWARD
 APPROACH REQUIRED AND SHALL EXTEND
 MAXIMUM 19" UNDERNEATH THE SINK.
 D. EXPOSED PIPES & SURFACES 11-4.24.6
 E. FAUCETS 11-4.24.7
 2) PER BUILDING OFFICAL CABINET DOORS
 SHALL NOT BE IN CLEAR FLOOR SPACE FOR
 SINKS AND A CLEAR OPENING IS REQUIRED.
 3) SHOW A TURNING AREA IN THE COFFEE
 STATION ROOM. SECTION 104.2.3.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]