| 2005-04-25 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | | | | 1) SINKS IN CONFERENCE ROOM, 707, AND | | | COFFEE STATION, 702, SHALL BE ACCESSIBLE | | | PROVIDE THE FOLLOWING INFORMATION ON | | | EACH DETAIL SHEET A-3.0: | | | A. KNEE CLEARANCE 11-4.24.3 | | | B. SINK DEPTH 11-4.24.4 | | | C. CLEAR FLOOR SPACE 11-4.24.5, FORWARD | | | APPROACH REQUIRED AND SHALL EXTEND | | | MAXIMUM 19" UNDERNEATH THE SINK. | | | D. EXPOSED PIPES & SURFACES 11-4.24.6 | | | E. FAUCETS 11-4.24.7 | | | 2) PER BUILDING OFFICAL CABINET DOORS | | | SHALL NOT BE IN CLEAR FLOOR SPACE FOR | | | SINKS AND A CLEAR OPENING IS REQUIRED. | | | 3) SHOW A TURNING AREA IN THE COFFEE | | | STATION ROOM. SECTION 104.2.3. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|