| Plan Review Notes For Permit 05040550 |
| Permit Number |
05040550 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-04-11 00:00:00 | DENIED | | | | | | 1) SPECIFY THE MEAN ROOF HEIGHT OF THE | | | STRUCTURE ON THE APPLICATION. IF THE | | | MEAN ROOF HEIGHT EXCEEDS THE LEAST | | | HORIZONTAL DIMENSION OF THE STRUCTURE OR | | | 60 FEET WHICHEVER IS LESS, CALCULATIONS | | | FOR THE UPLIFT PRESSURES FOR THE ROOFING | | | FROM AN ENGINEER OR ARCHITECT IS | | | REQUIRED. FBC 1606.2.1 | | | | | | 2) THE NOA THAT WAS SUBMITTED IS FOR | | | WOOD DECK. DO THESE CONDOS HAVE WOOD OR | | | CONCRETE DECKS? SPECIFY THE DECK | | | MATERIAL ON THE APPLICATION. | | | | | | 3) THE FLORIDA PRODUCT APPROVAL FL735 | | | HAS A DIFFERENT NOA # POSTED ON THE | | | WEBSITE THAN THE ONE THAT WAS SUBMITTED. | | | PLEASE SUBMIT THE CORRESPONDING NOA. | | | | | | 4) INDICATED THE APPROVED ASSEMBLY FROM | | | THE NOA THAT WILL BE INSTALLED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|