Plan Review Notes
Plan Review Notes For Permit 05040486
Permit Number 05040486
Review Stop E
Sequence Number 1
Notes
Date Text
2005-04-20 00:00:00******** UNSAT ***********
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS FOR NEW AND CORRELATE WITH
 SUBMITTED PANEL SCHEDULE.
 PLEASE INCLUDE ALL CONDUCTOR SIZES FOR
 BRANCH CIRCUITS.
 215.5,310.16,240.4
  
 2)NOTE: PLEASE SEE 424.3B FOR MIN OCP FO
 AHU/RTU 125%.
  
 3)NOTE: PLEASE SEE RISER DIAGRAM
 ATTACHED TO PLANS SEEM TO INDICATE AN
 ENTIRE NEW SERVICE?
 IF SO, PLEASE INCLUDE ALL INFORMATION
 FOR A NEW INSTALLATION. IF EXISTING,
 PLEASE INDICATE.
 215.5
 PLEASE SEE SEC'S SHOWN DO NOT MEET 240.3
 PLEASE SEE MIN SIZING OF SEC'S FOR
 DEVICES RATED OVER 800A'S TO MEET OR
 EXCEED OCP/DEVICE.
 GROUNDING ELECTRODE SYSTEM ? 250.50
 AIC RATINGS FOR ALL. 110.9
  
 4)NOTE: PLEASE SEE FBC 104.2.1
 ALL PLANS/DRAWING ARE REQUIRED TO HAVE
 THE PRINTED NAME AND SIGNATURE OF PERSON
 RESPONSIBLE FOR PLANS.
  
 5)NOTE: PLEASE SEE FAC 61G1-16.004 AND
 FS 481.219 FOR ARCHITECTUAL FIRM AND
 MISSING INFORMATION REQUIRED ON TITLE
 BLOCKS.
 THIS IS REQUIRED ON ALL SHEETS AND FOR
 ALL TRADES WHEATHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 6)NOTE: PLEASE SEE ALL CONTINUOUS LOADS
 ARE TO BE SHOWN AT 125%.
 LIGHTING/LARGEST MOTOR.
 215.3,230.42 ETC.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHOULD BE SUBMITTED FOR
 REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  