| Plan Review Notes For Permit 05040464 |
| Permit Number |
05040464 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-04-20 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | FBC-2001 CHAPTER 1 | | | | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2001 | | | FUEL GAS CODE. - ALSO SHOW WHERE | | | EXISTING GAS PIPE CONNECTS TO THE GAS | | | SYSTEM AND INDICATE PIPE SIZE. | | | 2. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2001 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES (A)(3). - SHOW THE | | | DISTANCE TO THE MOST REMOTE OUTLET ON | | | THE EXISTING GAS SYSTEM. | | | 3) ALL DRAWINGS AND SPECIFICATIONS SHALL | | | BEAR THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN. | | | SECTION 104.2.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | | | | | | | | | | | | | |
|