| 2005-04-13 00:00:00 | ********* UNSAT ********* |
| | |
| | 1)NOTE: PLEASE CLARIFY RISER, IT APPEARS |
| | TO SHOW A METER/MAIN COMBO?? |
| | PLEASE SEE RISER APPEARS TO SHOW A FEED |
| | GOING OUT OF THE TOP OF EQUIPMENT TO A |
| | SUB-PANEL? |
| | 215.5 |
| | PLEASE PROVIDE A PANEL SCHEDULE FOR |
| | EQUIPMENT OUTSIDE IF INDEED A PANEL. |
| | |
| | 2)NOTE: PLEASE CLARIFY IF LOAD SHOWN FOR |
| | POOL HEATER IS THE LOAD ALREADY FIGURED |
| | AT 125% FOR CONTINUOUS LOADS. |
| | 215.3,230.42 ETC. |
| | |
| | 3)NOTE: PLEASE SEE RISER SHOWS A 300A |
| | MAIN WITH NO OCP SHOWN FOR SUB PANEL. |
| | 300A MAIN ON 2/0'S?? |
| | 240.4,310.15B6 |
| | |
| | 4)NOTE: PLEASE SEE 250.66 FOR MIN |
| | GROUNDING ELECTRODE CONDUCTOR. #2 MIN |
| | 310.15B6 |
| | |
| | 5)NOTE: PLEASE SEE 210.52D FOR MISSING |
| | BATH RECEPTS WITHIN 3' OF SINK. |
| | |
| | 6)NOTE: PLEASE SEE MISSING A/C |
| | DISCONNECTS FOR AC/ CU'S AND AHU'S. PER |
| | 440.11 AND CLEARENCE PER 110.26 |
| | |
| | 7)NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210.8A-6 |
| | SEE ISLAND. |
| | |
| | 8)NOTE: PLEASE SEE 210.8A2 FOR GARAGES. |
| | |
| | 9)NOTE: PLEASE SEE PLANS ARE MISISNG ALL |
| | SERVICE EQUIPMENT?? UNABLE TO REVIEW |
| | LOCATIONS FOR CODE COMPLIANCE AT THIS |
| | TIME.215. |
| | |
| | 10)NOTE:SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | :PLEASE SEE MISSING SD LEADING TO FLOOR |
| | ABOVE: |
| | |
| | 11)NOTE: PLEASE SEE MISSING FOOTER STEEL |
| | FOR GROUNDING ELECTRODE REQUIRED. 250.50 |
| | |
| | 12)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | PLEASE SEE MANY OF THE ABOVE ITEMS HAVE |
| | BEEN REDLINED ON ONE SET OF PLANS. |
| | |
| | PLEASE REMOVE ALL OLD VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO TWOM |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE SET/COPY OF OLD SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |