| 2005-05-06 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1.) A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED, FS713.13. |
| | |
| | 2.) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.561-233-5025 |
| | |
| | 3.) A ROOF PERMIT NUMBER WAS NOT |
| | ASSIGNED.THIS TYPE OF ROOF IS NOT |
| | WITHIN THE SCOPE OF YOUR GC LICENSE, |
| | FS489. |
| | |
| | 4.)SHOW LANDING DIMENSION FOR STAIRS. |
| | |
| | 5.)PROVIDE A STRUCTURAL DETAIL FOR THE |
| | STAIRS. |
| | |
| | 6.)FLORIDA STATE OR LOCAL PRODUCT |
| | APPROVALS REQUIRED IN ADDITION TO THE |
| | NOAS PROVIDED, FAC9B72. |
| | WWW.FLORIDABUILDING.ORG. |
| | |
| | 7.)SUBMIT THE FOLLOWING PRODUCT |
| | APPROVALS: |
| | FIXED GLASS WINDOW |
| | MULLION |
| | |
| | 8.)CONNECTION DETAIL 5, A7, LUS210-3 |
| | FASTENING CONFLICTS WITH CATALOG.CHECK |
| | ALL CONNECTORS.IF YOU SPECIFY |
| | FASTENING IN CONFLICT WITH |
| | MANUFACTURER?S SPECIFICATIONS A LOCAL |
| | PRODUCT APPROVAL IS REQUIRED FAC9B72. |
| | |
| | 9.)PROVIDE DRAFTSTOP SCHEDULE, 2ND |
| | FLOOR FRAMING PLAN, FBC705.3. |
| | |