| Plan Review Notes For Permit 05040418 |
| Permit Number |
05040418 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-09-12 00:00:00 | 1. SEPERATE PLANS AND PERMITS REQUIRED | | | FOR FIRE SPRINKLER SYSTEM MODIFICATIONS. | | | | | | 2. NO EMERGENCY LIGHTS OR EXIT SIGNS | | | SHOWN IN EXISTING WAREHOUSE. IF | | | EXISTING ENSURE PROPER FUNCTION, IF | | | NONE, PLEASE INSTALL. | | | | | | 3. CARE SHOULD BE TAKEN NOT TO PAINT | | | ANY OF THE REQUIRED FIRE SPRINKLER | | | HEADS DURING PAINTING OPERATIONS. | | | | | | 4. BUILDING ADDRESS REQUIRED ON | | | PROPER ELEVATION. A MINIMUM OF AT | | | LEAST 6" HIGH NUMBERS ARE REQUIRED. | | | | | | 5. NEW HANDRAILS AND GUARDRAILS TO | | | MEET THE PRESCRIPTIVE STRENGTH | | | REQUIREMENTS OF BUILDING AND FIRE | | | CODE REQUIREMENTS. | | | | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | | | | 804-4709 PHONE | | | 804-4774 FAX |
|