| Plan Review Notes For Permit 05040418 |
| Permit Number |
05040418 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-09-03 00:00:00 | ** REDLINED PLANS** | | | | | | PLANS REFERENCE WRONG ELECTRICAL CODE. | | | WE ARE UNDER THE 2002 NEC. | | | | | | KEY NOTE ON E-1.0 #4 MENTIONS EXT/EM | | | LTS WIRED TO A-17. | | | PLEASE SEE 700.12E, WHICHREQUIRES THE | | | BRANCH CIRCUIT FEEDING THE UNIT | | | EQUIPMENT SHALL BE THE SAME BRANCH | | | CIRCUIT AS THAT SERVING THE NORMAL | | | LIGHTING IN THE AREA AND CONNECTED AHEAD | | | OF ANY LOCAL SWITCHES. | | | | | | BOTH ABOVE REDLINED, NO CORRECTIONS | | | NEEDED AT THIS TIME. IF PLANS HAVE | | | REVISIONS DIRING CONSTRUCTION, PLEASE | | | MAKE CORRECTIONS AT THAT TIME. |
|