2005-07-12 00:00:00IN ELEC FOR REVIEW.
 ************* UNSAT 2ND REVIEW *******
  
 PLEASE SEE PLAN HAVE ONLY BEEN SUBMITTED
 FOR "PLAN REVIEW" ONLY AND NOT FOT
 PERMIT.
  
 ************************************
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1)NOTE: NOTE #1 NO, PLEASE SHOW
 CIRCUITING AND CORRELATE WITH PANEL
 SCHEDULE. PLEASE SEE A NOTE WAS ADDED TO
 COMPLY WITH NEC 2005 700.12E.
 PLEASE SEE FBC 104.2.1 WHICH STATES THE
 TECHNICAL CODES SHALL NOT BE QUOTED FOR
 INFORMATION REQUIRED ON PLANS.
 PLEASE SEE NEW NOTE:
 PLEASE SEE PLANS MENTIONS 2005 NEC, WE
 ARE CURRENTLY UNDER THE 2002 NEC.
  
 2)NOTE: NOTE #2 OK.
  
 3)NOTE: NOTE #3 NO, ? IT IS UNCLEAR
 WHERE "SHOWROOM" WINDOW RECEPTS ARE?
 SHEET A2.0 SHOWS WINDOWS ON ELEVATION.
 PLEASE SEE 210.62,220.12
  
 4)NOTE: NOTE #4 OK, HOWEVER PLEASE SEE
 PREVIOUS NOTE FOR ADJUSTMENT PER 220.12
  
 5)NOTE: NOTE #5 OK, NEW MAIN SHOWN.
  
 6)NOTE: NOTE #6 NO, PLEASE SEE EQUIPMENT
 GROUNDING CONDUCTOR STILL BEING SHOWN
 BEFORE FIRST MEANS OF DISCONNECT(S).
 250.6,250.24.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE COPY OF OLD/VOIDED
 SHEETS FOR REFERENCE ONLY.
  
 PLEASE SEE PLANS HAVE ONLY BEEN
 SUBMITTED FOR "PLAN REVIEW".
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717