| Plan Review Notes For Permit 05040418 |
| Permit Number |
05040418 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-05-26 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | | | | 1. PER TABLE 403.1 A DRINKING FOUNTAIN | | | AND A SERVICE SINK ARE REQUIRED. PLEASE | | | INDICATE IF THESE FIXTURES ARE EXISTING. | | | 2. SHT CVR CODE IN EFFECT IS FBC-2001 | | | NOT 2003 AS SHOWN. PLEASE CORRECT | | | APPLICABLE CODES. SECTION 104.2.1. | | | 3. SHTS A1.2 AND A1.3 (DETAIL #2) THE | | | FOLLOWING INFORMATION SHALL BE INDICATED | | | TO SHOW COMPLIANCE WITH SECTION 11-4.24 | | | AND ALL SUBSECTIONS: | | | A. KNEE CLEARANCE 11-4.24.3 | | | B. SINK DEPTH 11-4.24.4 | | | C. CLEAR FLOOR SPACE 11-4.24.5 SHALL BE | | | FORWARD APPROACH AND EXTEND MAXIMUM 19" | | | UNDERNEATH THE SINK. | | | D. EXPOSED PIPES AND SURFACES 11-4.24.6 | | | E. FAUCETS 11-4.24.7 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|