2005-05-23 00:00:00DENIED:PLAN CHECK ONLY
  
 1.PLAN SHEET M2., RTU CURB DETAIL DOES
 NOT INDICATE THE REQUIRED HEIGHT OF THE
 CURB.PER 2001 FBC 1511.7, A MINIMUM OF
 8" ABOVE THE ROOF SURFACE IS REQUIRED.
  
 2.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS.
  
 3.INDICATE ACCESS TO EQUIPMENT LOCATED
 ON THE ROOF.PRE 2001 FBC/M 306.5,
 WHERE ACCESS TO EQUIPMENT LOCATED ON
 ROOFS IS GREATER THAN 16 FT, A PERMANENT
 MEANS OF ACCESS IS REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  
  