| Plan Review Notes For Permit 05040418 |
| Permit Number |
05040418 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-05-04 00:00:00 | 1) ALL CONSTRUCTION, ALTERATION AND | | | DEMOLITION TO COMPLY WITH NFPA 241. | | | | | | 2) LIFE SAFETY, NFPA 101, 2003 EDITION | | | SHALL BE COMPLIED WITH. | | | | | | 3) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE | | | ALARM REMODELS. | | | | | | 4) EXTERIOR STAIRS LOCATED AT THE SOUTH | | | SIDE OF THE BUILDING ARE REQUIRED TO | | | HAVE HANDRAILS ON BOTH SIDES. | | | | | | 5) DOES THE SHOWROOM MEET CRITERIA TO | | | ALLOW FOR A SINGLE EXIT? | | | | | | 6) ADDITIONAL EXIT SIGNS MAY BE REQUIRED | | | IFNECESSARY AT THE TIME OF THE FIELD | | | INSPECTION. | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 835-2910 OR 805-6722 |
|