| Date |
Text |
| 2005-04-21 00:00:00 | ********* UNSAT *********** |
| | |
| | PLEASE SEE PLANS ONLY SUBMITTED FOR |
| | "PLAN REVIEW " AT THIS TIME AND NOT |
| | SUBMITTED FOR PERMIT. |
| | |
| | 1)NOTE: PLEASE INCLUDE ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH PANEL SCHEDULES |
| | TO BE SUBMITTED. |
| | PLEASE ALSO SEE 700.12E FOR CIRCUITING |
| | OF EM/EXT LTS |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE PLACE AREA DESIGNATIONS |
| | ON PLANS. |
| | |
| | 3)NOTE: PLEASE SEE 210.62 FOR POSSIBLE |
| | "SHOW WINDOW" RECEPTS REQUIRED AND |
| | PLEASE ALSO SEE 210.12 FOR LOAD |
| | CALCULATIONS. |
| | |
| | 4 )NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| | PLEASE SHOW PER |
| | 220.3,220.10,220.11,220.13 ETC. |
| | PLEASE ALSO SHOW ALL CONTINUOUS LOADS |
| | AT 125% PER 215.3,230.42 |
| | |
| | 5)NOTE: PLEASE SEE NEW A/C DISC'S |
| | ATTACHED TO GUTTER NOW APPEAR TO MAINS |
| | 4OF 5 AND 5OF 5? |
| | PLEASE LABEL IF INDEED THIS IS THE CASE. |
| | |
| | 6)NOTE: PLEASE SEE 250.6,250.24, |
| | EQUIPMENT GROUNDING CONDUCTORS ARE ONLY |
| | INSTALLED AFTER THE FIRST MEANS OF |
| | DISCONNECT. |
| | |
| | 7)NOTE: PLEASE BE SURE TO REMOVE ALL |
| | OLD/VOIDED SHEETS FROM SETS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | PLEASE ONLY SUBMIT ONE SET OF OLD SHEETS |
| | FOR REFERENCE. |
| | |
| | PLEASE BESURE TO SEE ANY POSSSIBLE |
| | COMMENTS FROM OTHER REVIEWER(S) WHICH |
| | MAY AFFECT ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| 2005-04-20 00:00:00 | IN ELEC FOR REVIEW. |