| Notes |
| Date |
Text |
| 2005-05-02 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PROVIDE SPECS FOR THE GENERATOR, ATS | | | AND ALL RELATED EQUIPMENT. | | | | | | 2} PROVIDE A SCHEMATIC INDICATING | | | COMPLIANCE WITH ARTICLES 445,700.6 AND | | | 702 NEC. | | | | | | 3} PLEASE INDICATE THE LOAD CALCULATION | | | FOR THE CIRCUITS BEING FED FROM THE | | | EMERGENCY PANEL. NOTE: CANNOT FEED 300 | | | AMP SERVICE FROM A 10K GENERATOR. SEE | | | 700.5. | | | | | | 4} INDICATE THE PRIME MOVER FOR THE | | | GENERATOR. | | | | | | 5} PLEASE PROVIDE A CALCULATION | | | INCLUDING ALL ADDED LOADS IMPOSED,ALL | | | EXISTING LOADS AND THE EXISTING OR | | | PROPOSED SERVICE SPECIFICATIONS PER | | | 215.15. | | | | | | 6} THE PLANS MUST BE SIGNED AND SEALED | | | PER 481 FS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|