| Plan Review Notes For Permit 05040310 |
| Permit Number |
05040310 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-05-04 00:00:00 | 1) PLEASE PROVIDE PRODUCT CUT SHEETS | | | REGARDING THE GENERATOR AND ASSOCIATED | | | FUEL. | | | | | | 2) NFPA 704 MARKINGS ARE REQUIRED TO BE | | | POSTED ON OR IN THE VICINITY OF THE FUEL | | | TANK. | | | | | | 3) PROTECTION OF THE GENERATOR AND FUEL | | | TANK MAY BE REQUIRED IF SUBJECT TO | | | MECHANICAL DAMAGE. | | | | | | 4) SEPARATE SHOP DRAWING AND PERMIT IS | | | REQUIRED FOR FIRE ALARM SYSTEM REMODEL. | | | | | | 5) ALL PRECAUTIONS AND STANDARDS | | | REGARDING STATIC ELECTRICITY TO BE | | | COMPLIED WITH. | | | | | | 6) PLEASE PROVIDE INFORMATION PERTAINING | | | TO VENT PIPE LOCATION AND DIAMETER. | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 835-2910 OR 805-6722 |
|