Plan Review Notes
Plan Review Notes For Permit 05040310
Permit Number 05040310
Review Stop E
Sequence Number 1
Notes
Date Text
2005-04-25 00:00:00********** UNSAT *************
  
 1)NOTE: PLEASE SUBMIT MANUFACTURE CUT
 SHEETS FOR GENERATOR, SUB BASE TANK .
  
 2)NOTE: PLEASE SEE OTHER REVIEWER NOTES
 PERTAINING TO 6000 GALLON FUEL TANK.
  
 3)NOTE: PLEASE SEE FIRE ALARM
 SYSTEM/WORK TO BE UNDER A SEPARATE
 PERMIT.
 PLEASE ALSO SEE LIGHTING PROTECTION IS
 ALSO REAUIRED TO BE UNDER A SEPARATE
 PERMIT.
  
 4)NOTE: PLEASE CORRELATE BUS RATINGS AND
 PANEL RATINGS OF NUMEROUS PANELS.
 \PLEASE SEE PANELS SHOWN AS 100A AND
 225A, 600A AND 500A, 600A AND 400A ETC
 ETC.
  
 5)NOTE: PLEASE CORRELATE OCP , LOAD ON
 EQ SHOWN AT 536A'S ON 225A BUS AND 600A
 MLO?? SEE RATING OF ATS-EQ, PANEL EQ,
 OCP AT MSB ETC.
 PLEASE SEE 310.15,240.4,215.5 ETC.
 NEC 2002
  
 6)NOTE: PLEASE CORRELATE RISER AND PANEL
 SCHEDULE FOR MSB, ONE SHOWS MLO AND THE
 OTHER INDICATES A MCB?
 PLEASE SEE A MCB IS REQUIRED.
 230.71
  
 7)NOTE: PLEASE SEE 620.23,620.24 FOR MIN
 CIRCUITS REQUIRED IN ELEV MACHINE RMS.
  
 8)NOTE: PLEASE CORRELATE ELECTRICAL ROOM
 LAYOUTS. PLEASE SEE "E-4".
 215.5
  
 9)NOTE: PLEASE SEE EGD, PLEASE EXPLAIN
 HOW POWER IS COMING DIRECTLY FROM GEN.
 AND DOES NOT SEEM TO GO THROUGH ANY
 TRANSFER SWITCH??
  
 10)NOTE: PLEASE SUBMIT A COPY OF
 CONTRACT TO VERIFY VALUE FOR SCOPE OF
 WORK SHOWN. PLEASE SEE FBC 104.6.5,
 VALUE FOR SCOPE OF WORK IS BASED ON ALL
 LABOR AND MATERIALS, EVEN IF OWNER
 SUPPLIED.
  
 11)NOTE: PLEASE SEE ELECTRICAL ROOM IS
 SHOWN AS MAINT/STORAGE ROOM. PLEASE SEE
 THIS IS REQUIRED DEDICATED ELECTRICAL
 SPACE PER 110.26 AND SHALL NOT HAVE ANY
 MAINT/ STORAGE .
  
 PLEASE SEE ONE SET OF PLANS HAVE MANY OF
 THE ABOVE ITEMS REDLINED.
  
 PLEASE SEE COMMMENTS FROM OTHER
 REVIEWERS WHICH WILL HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETS AND INSERT ONLY NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
 6)NOTE: PLEASE
2005-04-22 00:00:00ELECTRICAL TO BE DENIED, NOTES TO
 FOLLOW.
2005-04-20 00:00:00IN ELEC FOR REVIEW.