2005-05-10 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)DETAIL C-E4 DOES NOT HAVE
 DIMENSIONS FOR THE FOOTING UNDER THE
 GENERATOR.NO STEEL IS SHOWN.PLEASE
 PROVIDE WEIGHT AND SIZE OF GENERATOR.
 E4, TOP LEFT CORNER, REFERS TO A
 "136'X52"X66" GENERATOR" AND A 6000
 GALLON FUEL TANK.REALLY 6000 GALLONS
 AND 136 FEET?
  
 2.)CONFIRM THAT THE CONCRETE CAN BEAR
 THE WEIGHT (AS OF YET UNDETERMINED) OF
 THE GENERATOR.
  