| Plan Review Notes For Permit 05040279 |
| Permit Number |
05040279 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-04-11 00:00:00 | *****UNSAT ***** | | | | | | 1)NOTE: PLEASE PROVIDE LAYOUT FOR NEW | | | KITCHEN/BATHS SHOWING EITHER EXISTING OR | | | NEW FOR ELECTRICAL . 210.52C1-5, 210.8A6 | | | 210.70, 210.52D,210.11C3 | | | DRAWING SHOWS LAYOUT FOR ENTIRE UNIT, | | | PLEASE IDENTIFY AREAS AND LOCATION OF | | | WORK TO BE DONE. | | | | | | 2)NOTE: PLEASE SEE FBC 104.2.1, WHICH | | | REQUIRES THE PRINTED NAME AND SIGNATURE | | | OF PERSON RESPONSIBLE FOR PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | |
|