| Notes |
| Date |
Text |
| 2005-04-15 00:00:00 | BUILDING PLAN REVIEW: FAILED | | | | | | 1. SHOW LOCATION OF STOREFRONT TO BE | | | INSTALLED. | | | | | | 2. SUBMIT FLORIDA PRODUCT APPROVALS FOR | | | THE STOREFRONTS BEING INSTALLED. | | | | | | 3. ARE THERE EXISTING STORM PANELS? | | | FBC2001 REQUIRES STORM PANEL PROTECTION. | | | | | | 4. CLARIFY "SWITCH DOOR GLASS" | | | | | | 5. A NOTICE OF COMMENCEMENT MUST BE | | | SUBMITTED BEFORE A PERMIT CAN BE ISSUED. | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 805-6713 |
|