Plan Review Notes For Permit 05040221
Permit Number 05040221
Review Stop E
Sequence Number 4
Notes
Date Text
2006-10-20 07:40:52 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK
 MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002
 FAC.
  
 2} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 3} THE GROUNDS FROM THE METER TO BOTH FIRST MEANS OF
 DISCONNECT CREATE PARALLEL GROUND PATHS. REMOVE FROM
 PLAN.
  
 4} THE NOTE AT THE BOTTOM OF THE PANEL SCHEDULE
 INDICATES A 400 AMP SERVICE, THE SERVICE CONDUCTORS ARE
 250 MCM, WHICH IS ONLY RATED FOR 300 AMPS PER
 310.15(B)(6). PLEASE CORRELATE.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718
  
  