2005-09-09 00:00:00BUILDING REVIEW THIRD CHECKLIST:
 1- A) NOTICE OF COMMENCEMENT DESCRIPTION
 NEEDS TO SPECIFY CONSTRUCTION OF A NEW 2
 STORY HOUSE. ANOTHER INFORMATION WAS
 DESCRIBED, BUT THERE IS NOT INDICATION
 OF A NEW 2 STORY HOUSE. REVISE AS REQ'D.
  
 B) NOTICE OF COMMENCEMENT NEEDS TO BE
 RE-RECORDED. IT EXPIRES AFTER 90 DAYS OF
 RECORDING IF WORK IS NOT STARTED. FL
 STATUTE 713.13(1)(G).
  
 2- SETBACKS SHOWN IN SURVEY AND IN SHEET
 A1 SITE PLAN DON'T MATCH REVISE AS REQ'D
  
 3- A) ROOF LOADING CHART IN PAGE A7 WAS
 CHANGED AND NOW IT'S MISSING THE ATTIC
 LIVE LOAD OF 30PSF OR 10PSF IS USED FOR
 STORAGE OR NON STORAGE AS REQUIRED BY
 TABLE 1604.1 FBC 2001.
  
 B) WIND INFORMATION ON SHEET A1 CHANGED
 FROM FBC 2001 TO ASCE. NEED TO IDENTIFY
 WHICH EDITION OF ASCE WAS USED BECAUSE
 THE EDITION ADOPTED BY THE CURRENT
 BUILDING CODE IS ASCE 7-98.
  
 4- ROOF SHEATHING SPECS ON SHEET A7 WERE
 CHANGED. FASTENERS WERE CHANGED FROM 8D
 RING SHANK TO 8D COMMON NEED TO REVISE
 AGAIN TO COMPLY WITH TABLE 2306.1 OF
 CITY AMENDMENTS TO FBC 2001. PREVIOUS
 COMMENT WAS TO SPECIFY FASTENER SPACING
 FOR ZONE 3 AREAS TO COMPLY WITH CITY
 AMENDMENTS. FASTENER SPECIFED AT THAT
 TIME WAS OK.
  
 5- REVISE SPECS FOR CEILING INSTALLATION
 AT ENTRY AND REAR PORCH AS REQ'D BY ASTM
 C926 AND ASTM C1063. FROM PREVIOUS
 COMMENT INFORMATION WAS CHANGED FOR
 POWER ACTUATED FASTENERS, BUT NOR FOR
 HAND NAILED FASTENERS.
  
 6- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A) ENTRY DOORS. FLORIDA PRODUCT APPROVAL
 SUBMITTED IS FOR MODEL FD-6000 VINYL
 INSWING DOOR. DADE COUNTY NOA SUBMITTED
 IS FOR SWD-101 OUTSWING ALUMINUM DOOR.
 NEED MATCHING INFORMATION.
  
 B) FRENCH DOORS WITH AND WITHOUT
 SIDELITES. DADE COUNTY NOA REPORT AND
 DRAWINGS SUBMITTED DON'T MATCH. REVISE.
  
 C) GARAGE SIDE DOOR.
  
 D) SINGLE HUNG WINDOWS.
  
 E) WINDOW MULLIONS.
  
 F) GARAGE DOORS DESIGN PRESSURES WERE
 CHANGED. NOW NEEDS GARAGE DOORS THAT
 MEET THE CALCULATED DESIGN PRESSURES.
  
 7- SHEET A4: TOTAL AREA CALCULATIONS
 DON'T ADD UP CORRECTLY. REVISE AS REQ'D.
  
 8- CLARIFY IF USING THE 2ND FLOOR
 FRAMING PLAN AS A DIAPHRAGM TO RESIST
 THE LATERAL LOADS OR NOT. PROVIDE
 COMPLETE ENGINEERING CALCULATIONS
 SHOWING HOW DOES THE STRUCTURE COMPLIES
 WITH SECTIONS 2105 (LATERAL STABILITY)
 AND 2107 (LATERAL SUPPORT) OF FBC 2001.
 SEC. 104.2.1.2 CITY AMENDMETNS TO FBC
 2001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.