Plan Review Notes
Plan Review Notes For Permit 05040221
Permit Number 05040221
Review Stop P
Sequence Number 1
Notes
Date Text
2005-04-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHT A9 SANT. RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IT MEET
 THE CODE REQUIREMENTS. CORRECT THE
 FOLLOWING:
 A. WATER CLOSET IN THE 1/2 BATH IS NOT
 VENTED. SECTION 901.2.1.
 B. EXTRA LAV SHOWN ON THE RISER FOR
 BATH #4 2ND FLOOR. SECTION 104.2.1.
 C. SANT. RISER DIAGRAM DOES NOT REFLECT
 THE PIPING LAYOUT ON THE PLUMBING FLOOR
 PLAN. THE FLOOR PLAN PIPING DOES MEET
 CODE AND IF THE RISER DIAGRAM REFLECTS
 THE PIPING ON THE FLOOR PLAN, IT WILL
 MEET CODE REQUIREMENTS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]