| Notes |
| Date |
Text |
| 2005-04-21 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1. SHT A9 SANT. RISER DIAGRAM DOES NOT | | | REFLECT THE FLOOR PLAN, NOR DOES IT MEET | | | THE CODE REQUIREMENTS. CORRECT THE | | | FOLLOWING: | | | A. WATER CLOSET IN THE 1/2 BATH IS NOT | | | VENTED. SECTION 901.2.1. | | | B. EXTRA LAV SHOWN ON THE RISER FOR | | | BATH #4 2ND FLOOR. SECTION 104.2.1. | | | C. SANT. RISER DIAGRAM DOES NOT REFLECT | | | THE PIPING LAYOUT ON THE PLUMBING FLOOR | | | PLAN. THE FLOOR PLAN PIPING DOES MEET | | | CODE AND IF THE RISER DIAGRAM REFLECTS | | | THE PIPING ON THE FLOOR PLAN, IT WILL | | | MEET CODE REQUIREMENTS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|