2005-04-13 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} LOAD CALCULATION PER 220.30 OR 220
 I,II AND III. 220.16, 220.18,
 210.11(C)(3) NOT ADDRESSED OR INCORRECT.
 2002 NEC.
  
 2} IF THE GROUND IS CARRIED TO THE
 DISCONNECTS FROM THE METER AN ISOLATION
 KIT MUST BE INSTALLED IN THE ENCLOSURE.
  
 3} THE FAMILY ROOM NEEDS A RECEPTACLE
 ADDED TO COMPLY WITH 210.52(A).
  
 4} THE WATER HEATER WAS NOT INCLUDED IN
 THE CALCS.
  
 5} A SMOKE DETECTOR IS REQUIRED ON THE
 FIRST FLOOR AT THE STAIR TO COMPLY WITH
 905.2.2 FBC 2001.
  
 6} A RECEPTACLE PER 210.63 MUST BE
 INSTALLED IN THE ATTIC FOR AHU SERVICE.
  
 7} ALL RECEPTACLES ON THE LANAI MUST
 COMPLY WITH 210.52(E)GFI.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  