| Notes |
| Date |
Text |
| 2005-04-13 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} LOAD CALCULATION PER 220.30 OR 220 | | | I,II AND III. 220.16, 220.18, | | | 210.11(C)(3) NOT ADDRESSED OR INCORRECT. | | | 2002 NEC. | | | | | | 2} IF THE GROUND IS CARRIED TO THE | | | DISCONNECTS FROM THE METER AN ISOLATION | | | KIT MUST BE INSTALLED IN THE ENCLOSURE. | | | | | | 3} THE FAMILY ROOM NEEDS A RECEPTACLE | | | ADDED TO COMPLY WITH 210.52(A). | | | | | | 4} THE WATER HEATER WAS NOT INCLUDED IN | | | THE CALCS. | | | | | | 5} A SMOKE DETECTOR IS REQUIRED ON THE | | | FIRST FLOOR AT THE STAIR TO COMPLY WITH | | | 905.2.2 FBC 2001. | | | | | | 6} A RECEPTACLE PER 210.63 MUST BE | | | INSTALLED IN THE ATTIC FOR AHU SERVICE. | | | | | | 7} ALL RECEPTACLES ON THE LANAI MUST | | | COMPLY WITH 210.52(E)GFI. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | |
|