Plan Review Notes
Plan Review Notes For Permit 05040221
Permit Number 05040221
Review Stop B
Sequence Number 1
Notes
Date Text
2005-05-03 00:00:00BUILDING REVIEW CHECKLIST:
 1- PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING BACK STAMPED DRAWINGS AND PAID
 RECEIPT.
  
 2- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 3- SPECIFY 30PSF ATTIC LIVE LOAD AT
 ATTIC WITH STORAGE AREAS AND 10PSF ATTIC
 LIVE LOAD AT ATTIC WITHOUT STORAGE AREAS
 AS REQUIRED BY TABLE 1604.1 FBC 2001.
  
 4- REVISE ROOF SHEATHING FASTENING
 SPECS. SEE TABLE 2306.1 CITY AMENDMENTS
 TO FBC 2001 FOR TYPE OF NAIL AND SPACING
 TO BE USED ON ZONE 3 OF ROOF WHEN MEAN
 ROOF HEIGHT IS MORE THAN 25'-0". REVISE
 SPECIFICATIONS AND DETAILS AS REQUIRED.
  
 5- CONTRACTOR INSURANCE EXPIRED ON
 4-22-05. UPDATE AS REQUIRED.
  
 6- OWES $965.81 FOR UPDATED VALUATION
 AND RADON FEES.
  
 7- REVISE NOTES ON SHEET A4 AND A5
 REGARDING INSPECTION HOLES. 3/4" HOLES
 ARE TOO SMALL. SEE ACI 530 AND SPECIFY
 CORRECT SIZE FOR INSPECTION AND CLEANOUT
 OPENINGS.
  
 8- HALF BATH IN 1ST FL TO HAVE DOOR THAT
 ALLOWS 29" MIN. CLEAR OPENING REQ'D BY
 SEC. 11-11 FBC 2001. REVISE AS REQUIRED.
  
 9- SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 104.2.1.1 CITY
 AMENDMENTS TO FBC 2001.
  
 10- SPECIFY DRAFTSTOPPING MATERIAL AND
 LOCATION IN2ND FLOOR FRAMING PLAN AS
 REQUIRED BY SEC. 2305.2.2 FBC 2001.
  
 11- PROVIDE DETAIL/SPECS FOR CEILING
 INSTALLATION AT ENTRY AND REAR PORCHES
 AND AT SECOND FLOOR BALCONIES. SEE ASTM
 C926 AND ASTM C1063. SPECIFY FASTENER
 TYPE AND SPACING. SEC. 2504.2 FBC 2001.
  
 12- OMIT ALL DETAILS THAT DON'T APPLY TO
 THIS PROJECT TO EXPEDITE REVIEW PROCESS.
  
 13- PROVIDE COMPLETE BBQ SPECS THAT
 CLEARLY STATE THAT BBQ IS DESIGNED TO BE
 INSTALLED IN THE PORCH OR LANAI.
  
 14- PROVIDE SOIL TEST REPORT (2 COPIES).
  
 15- CLARIFY WHY HOOPS ARE NOT REQUIRED
 ON CONCRETE BEAMS SPECIFIED ON BEAM
 SCHEDULE? PROVIDE COMPLETE ENGINEERING
 ANALYSIS. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.
  
 16- PROVIDE COMPLETE DETAILS/SPECS FOR
 WINDOW ATTACHMENT TO STEEL COLUMN AT
 MASTER BATHROOM WINDOWS. SEE WINDOWS
 PRODUCT APPROVAL FOR APPROVED
 INSTALLATION. SECTION 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 17- SPECIFY SMOKE DETECTOR ON FIRST
 FLOOR IN CLOSE PROXIMITY TO STAIRS. SEC.
 905.2.2 FBC 2001.
  
 18- DADE COUNTY NOAALONE ARE NOT
 AUTOMATICALLY FLORIDA PRODUCT APPROVALS.
 NEED TO PROVIDE FLORIDA PRODUCT APPROVAL
 OR APPLY FOR LOCAL PRODUCT APPROVAL FOR:
 A) ENTRY DOORS.
 B) FRENCH DOORS (WITH AND WITHOUT
 SIELITES).
 C) GARAGE SIDE DOOR.
 D) GARAGE DOORS (SEE CALCULATED DESIGN
 PRESSURES ON PLANS).
 E) SINGLE HUNG WINDOWS.
 F) WINDOW MULLIONS.
 G) ROOF TILE.
 H) TRUSS CONNECTORS SPECIFIED ON PLANS.
 I) STORM SHUTTERS. SEE COMMENT BELOW.
  
 19- PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS INCLUDING KEY PLAN AND
 COMPLETE INSTALLATION SCHEDULE. SEE
 ATTACHED SAMPLE. AND CLEARLY MARK ON
 SHUTTER DRAWINGS SPECIFIC MOUNTING
 CONDITIONS AND ANCHOR TYPE AND SPACING
 TO BE USED ACCORDINGTO THE DESIGN
 PRESSURES, EDGE DISTANCE, PANEL SPAN,
 CONNECTION TYPE AND STRUCTURE TO BE
 ATTACHED TO (MASONRY OR CONCRETE).
  
 20- SHEET A1: A) UPDATE GENERAL NOTE
 REGARDING ACI 318. SEE CHAPTER 35 FOR
 PROPER YEAR REFERENCE.
  
 B) WIND INFORMATION:
 * WHERE IS THE BASIC VELOCITY PRESSURE
 TAKEN FROM? THERE IS NO TABLE SHOWN ON
 CHAPTER 16 FBC 2001.
  
 **CLARIFY WHY TOTAL ROOF DEAD LOAD IS
 5PSF?. SEE SEC. 1606.1.2 FBC 2001.
 ALSO, NEED TO CONSIDER ACTUAL WEIGHT OF
 DEAD LOAD. EG: ROOF TILE ETC. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 ***CLARIFY NOTE REGARDING 4' MIN. LENGTH
 NO OPENINGS BET. REINFORCED CELLS. WHICH
 ARE THE SHEARWALLS SINCE PLANS SHOW MANY
 OPENINGS BETWEEN 4' INTERVALS?. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 SEE COMMENTS ON REVIEWED SET OF PLANS.
  
 21- SPECIFY FIREBLOCKING MATERIAL IN
 STAIR SECTION AS REQUIRED BY SEC.
 2305.1.4 FBC 2001.
 NOTE: FIREBLOCKING AND DRAFSTOPPING ARE
 TWO DIFFERENT THINGS.
  
 22- SHEET A4: A) EGRESS WINDOW NOTES ARE
 INCORRECT. SEE SEC. 1005.4.4 FBC 2001
 AND REVISE AS REQUIRED.
  
 B) REVISE WINDOW/DOOR STRUCTURAL BUCK
 DETAIL. SEE SEC. 1707.4.4.2 FBC 2001 FOR
 PROPER BUCK INSTALLATION.
  
 C) PROVIDE STRUCTURAL GARAGE BUCK DETAIL
 TO RECEIVE GARAGE DOOR. SEE GARAGE DOOR
 PRODUCT APPROVAL.
  
 D) SPECIFY SAFETY GLASS IN MASTER
 BATHROOM WINDOWS. SEC. 2405.2.1 FBC 2001
  
 E) PROVIDE COMPLETE DETAIL/SECTION AT
 CONSTRUCTION OF CONNECTION BETWEEN WALL
 IN BEDROOM #3 & FRONT WINDOW. SEE PLAN.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
 F) SPECIFY WIDTH OF STAIRCASE.
  
 23- SHEET A5: A) TYP. 2 STORY WALL
 SECTION: * SPECIFY FIREBLOCKING IN WALL
 SECTION. SEC. 2305.1.4 FBC 2001.
  
 ** SPECIFY HOW FIRE CUT IS ACCHIEVED TO
 COMPLY WITH SEC. 2305.4 FBC 2001.
  
 *** SPECIFY VENT SIZE, LOCATION AND
 SPACING. SEC. 2309.7 FBC 2001.
  
 **** 12'X8" MASONRY COLUMN DETAIL AND
 SPECS BELOW IT DON'T MATCH. NUMBER OF
 REBARS TO MATCH. REVISE AS REQUIRED.
  
 ***** SPECIFY COLUMNS THAT ARE LOCATED
 AROUND SAIRWELL TO SUPPORT 2ND FLOOR
 FRAMING. ALSO, SPECIFY TOP AND BOTTOM
 CONNECTION. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 NOTE: SAME THING APPLIES TO DETAIL ON
 SHEET A6.
  
 24- SHEET A7: A) REVISE/UPDATE TRUSS
 ANCHOR SCHEDULE. SEE LATEST MANUFACTURER
 CATALOGUE FOR CORRECT UPLIFT AND LATERAL
 LOADS.
  
 B) PROVIDE COMPLETE ENGINEERING ANALYSIS
 SHOWING WHY 2ND FLOOR TRUSSES DON'T NEED
 TO BE FASTENED TO THE WALL. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 C) SPECIFY CONNECTORS AT THE ENDS OF ALL
 FLOOR TRUSSES.
  
 D) SPECIFY/CLARIFY HOW ARE TRUSSES
 INSTALLED ABOVE GARAGE AREA. SEE PLANS.
 DO THEY GO THRU THE MASONRY WALL TO FORM
 THE MANSARD? SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.