| 2005-08-17 00:00:00 | BUILDING REVIEW THIRD CHECKLIST: |
| | |
| | 1- ARCHITECT WAS ASKED TO REVISE THE |
| | ROOF LOADS CHART IN SHEET A2. REVISION |
| | WAS DONE BY WHITING OUT THE ATTIC LIVE |
| | LOAD AS REQUIRED BY TABLE 1604.1 FBC |
| | 2001. NOW, CHART IS WRONG BECAUSE THE |
| | TOTAL LOAD WAS NOT REVISED ACCORDINGLY. |
| | TOTAL LOAD IS NOW 65PSF NOT 55PSF. |
| | REVISE AS REQUIRED. |
| | **NOTE: ARCHITECT TO SEE ATTACHED COPY |
| | OF FLORIDA STATUTE 553.80(2)(B)REGARDING |
| | MULTIPLE PLAN REVIEW DENIALS. |
| | |
| | 2- ENERGY CALCULATIONS: A) AGAIN, IF THE |
| | ENERGY CALCULATIONS ARE PREPARED BY THE |
| | ARCHITECT THEY NEED TO BE SIGNED AND |
| | SEALED AS REQUIRED BY CHAPTER 481 |
| | FLORIDA STATUTES. |
| | |
| | B) MISSING THE ADJACENT CEILING AREA. |
| | |
| | 3- A) CLEARLY IDENTIFY SINGLE HUNG |
| | WINDOWS TO BE USED TO REVIEW FOR |
| | COMPLIANCE WITH THE CALCULATED DESIGN |
| | PRESSURES. CIRCLE IN THE DADE COUNTY NOA |
| | DRAWINGS SPECIFIC WINDOW (GLASS TYPE) TO |
| | BE USED. |
| | B) CLARIFY WHY HIGHLIGHTED WINDOW TYPE |
| | IN SHEET 3 OF THE FLORIDA PRODUCT |
| | APPROVAL CALLS FOR 435 LITEHOUSE MODEL, |
| | WHILE DADE COUNTY NOA CALLS FOR 435 |
| | STORMBREAKER? IS THIS THE SAME MODEL. |
| | INFORMATION NEED TO MATCH INFORMATION |
| | SUBMITTED FOR FLORIDA PRODUCT APPROVAL. |
| | |
| | 4- NOTICE OF COMMENCEMENT EXPIRES AFTER |
| | 90 DAYS IF WORK IS NOT STARTED. NEED |
| | RE-RECORDED NOC. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT (561)805-6712. |