| 2005-07-22 00:00:00 | CHECKLIST: |
| | 1- ROOF LOADS CHART IN SHEET A2 IS |
| | WRONG. IT'S NOT TAKING INTO |
| | CONSIDERATION THE ATTIC LIVE LOAD |
| | REQUIRED BY TABLE 1604.1 FBC 2001. |
| | (30PSF LIVE LOAD FOR STORAGE OR 10PSF |
| | LIVE LOAD WITHOUT STORAGE). |
| | |
| | 2- STEPS AT ENTRY PORCH AND GARAGE DON'T |
| | COMPLY WITH SECTION 1007.3.1EXCEPTION |
| | #1. IT DOESN'T MEET THE REQUIRED RISER |
| | TREAD RATIO. |
| | |
| | 3- REVISE ENERGY CALCULATIONS AGAIN: |
| | A) IF THEY ARE PREPARED BY THE |
| | ARCHITECT, THEY NEED TO BE SIGNED, |
| | SEALED AND DATED AS REQUIRED BY CHAPTER |
| | 481 FLORIDA STATUTES. |
| | B) OVERHANG LENGTH AND HEIGHT ARE |
| | INCORRECT. SEE SEC. 601.2.A.3 CHAPTER 13 |
| | OF FBC 2001. |
| | C) OWNER/AGENT TO SIGN AND DATE BOTTOM |
| | OF FORM. |
| | D) SLAB ON GRADE PERIMETER CALCULATION |
| | DOESN'T MATCH PLANS. |
| | E) NEED ADJACENT CEILING AREA. |
| | |
| | 4- CLEARLY IDENTIFY SINGLE HUNG WINDOWS |
| | TO BE USED TO VERIFY COMPLIANCE WITH THE |
| | CALCULATED DESIGN PRESSURES SINCE |
| | PRODUCT APPROVAL SUBMITTED HAS SOME |
| | WINDOWS THAT DON'T MEET THOSE LOADS. |
| | |
| | 5- SPECIFICATIONS FOR WIRE LATH IN THE |
| | FASTENER SCHEDULE DON'T MATCH |
| | SPECIFICATIONS SHOWN ON PORCH SECTION. |
| | REVISE AS REQUIRED. |
| | |
| | 6- STAIR SECTION. CLEARLY INDICATE |
| | FIREBLOCKING IN STAIRWAY SECTION AS |
| | REQUIRED BY SEC. 2305.1.4 FBC 2001. |
| | (THERE WAS NOT LETTER ATTACHED WITH |
| | SUBMITTAL). |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |