| Plan Review Notes For Permit 05040194 |
| Permit Number |
05040194 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-04-20 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT A3 OF 4, SANITARY RISER DIAGRAM | | | DOES NOT MEET THE CODE REQUIREMENTS, NOR | | | DOES IT REFLECT THE FLOOR PLAN. | | | A) SECTION 909.1 KITCHEN SINK AND WASH | | | MACHINE SHALL NOT DRAIN INTO THE | | | WET-VENT FOR THE POWDER ROOM. THESE | | | FIXTURES SHALL DISCHARGE DOWNSTREAM OF | | | THE POWDER ROOM FIXTURES. | | | B) MASTER BATH SHOWS SHOWER ON FLOOR | | | PLAN, BUT TUB ON THE RISER DIAGRAM. | | | SECTION 104.2.1. | | | C) MASTER BATH SHOWS A LAV ON THE FLOOR | | | PLAN, BUT SHOWS A LAV ON THE RISER | | | DIAGRAM. SECTION 104.2.1. | | | | | | 2) SEE RED LINE CORRECTIONS ON ONE SET | | | OF PLANS. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|