| Plan Review Notes For Permit 05040155 |
| Permit Number |
05040155 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-05-16 00:00:00 | | | | PLEASE PROVIDE A CALCULATION | | | INCLUDING ALL ADDED LOADS IMPOSED,ALL | | | EXISTING LOADS AND THE EXISTING OR | | | PROPOSED SERVICE SPECIFICATIONS PER | | | 215.15. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|