Plan Review Notes
Plan Review Notes For Permit 05031931
Permit Number 05031931
Review Stop G
Sequence Number 1
Notes
Date Text
2005-04-18 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 1) AS REQUIRED BY 104.3.1.1 OF THE CODE,
 TWO OR MORE COPIES OF DRAWINGS WITH
 SUFFICIENT CLAIRTY AND DETAIL TO
 INDICATE THE NATURE AND CHARACTER OF THE
 WORK, SHALL ACCOMPANY THE APPLICATION
 FOR A PERMIT. - ONLY ONE ISOMETRIC HAS
 BEEN SUBMITTED. SECTION 104.2.1. -
 REDRAW THE ISOMETRIC WITH CORRECTIONS
 NOTED IN RED AND RESUBMIT.
 2) 1-1/4" PE PIPE IS REQUIRED FOR
 399,000 BTU'S AT 125'
 3) A RED TAG HAS BEEN ISSUED REQUIRING 4
 TIMES THE FEE. A BALANCE OF $151.00 IS
 REQUIRED FOR THE PERMIT.
  