| Plan Review Notes For Permit 05031898 |
| Permit Number |
05031898 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-04-06 00:00:00 | PERMIT APPLICATIONWAS SUBMITTED | | | WITHOUT PLANS.PLANS SUBMITTED WITH | | | BUILDING PERMIT ARE NOT COMPLETE. | | | PROVIDE THE FOLLOWING INFORMATION FOR | | | REVIEW: | | | - DISTANCE TO COMBUSTIBLES OR FIRE WRAP | | | INFORMATION. | | | - FPM WITHIN THE GREASE DUCT SYSTEM | | | AS PER 2001 FBC/M 506.3.6 | | | - PROVIDE MATERIAL OF GREASE DUCT IN | | | ACCORDANCE WITH 2001 FBC/M 506.3.3. | | | - GREASE DUCT TO HAVE A MINIMUM SLOPE | | | OF 1/4" PER FT. | | | - PROVIDE DETAIL FOR HANGING THE HOOD. | | | | | | SEE THE ATTACHED PROVISO, THIS WAS ON | | | THE APPROVED MECHANICAL PLANS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|