Plan Review Notes
Plan Review Notes For Permit 05031878
Permit Number 05031878
Review Stop B
Sequence Number 1
Notes
Date Text
2005-05-20 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC 1601.2.1CALCULATION SHEET C-8.
 GUARDRAIL CENTER POST WIND LOADING.THE
 BENDING MOMENT AT THE BASE OF THE POST
 APPEARS TO BE UNDER-ESTIMATED.THE
 GUARDRAIL IS 43" HIGH AND HAS ONLY ONE
 OPENING WHICH IS A CONTINUOUS 1-7/8"
 IMMEDIATELY ABOVE THE SLAB.THEREFOR
 THE 120.2 PSF WIND LOAD WILL ACT ON 41"
 HEIGHT OF GUARDRAIL, NOT 37.5" AS STATED
 IN THE CALCULATIONS. ALSO, THE RESULTANT
 FORCE WILL ACT AT 22.5" ABOVE SLAB
 LEVEL, NOT 18.75" ABOVE SLAB LEVEL AS
 STATED IN THE CALCULATION. THUS, THE
 BENDING MOMENT AT THE BASE OF THE CENTER
 POST IS 42,111 IN-LBS AND NOT 32,097
 IN-LBS AS STATED IN THE CALCULATIONS.
 IF THE SECTION MODULUS IS 1.566 IN***3,
 THIS WILL RESULT IN A BENDING STRESS
 FB(X-X) OF 26,891 PSI WHICH EXCEEDS THE
 ALLOWABLE 20,000 PSI. THIS COMMENT ALSO
 APPLIES TO THE POSTS ON CALCULATION
 SHEETS C-10 AND C-12.IF THE COMMENT IS
 CONSIDERED TO BE INCORRECT, PLEASE CALL
 TO DISCUSS. OTHERWISE, AMEND THE
 CALCULATION AND ADJUST THE DESIGN
 ACCORDINGLY.
  
 2) FBC 1601.2.1CALCULATION SHEET C-8
 AND C-10.GUARDRAIL POSTS.THE
 50 LBS/FT UNIFORMLY DISTRIBUTED LOAD
 SHOULD NOT BE APPLIED TO THE LENGTH OF
 THE POST, INSTEAD IT SHOULD BE APPLIED
 TO THE LENGTH OF SUPPORTED TOP RAIL AND
 ACT AS A POINT LOAD AT THE TOP OF THE
 POST.THIS CORRECTION WILL RESULT IN AN
 INCREASED BENDING MOMENT.AMEND THE
 CALCULATION.
  
 3) 61G15-23.002(2)FL. ADMIN. CODE.
 THE CALCULATION REPORT DOES NOT INCLUDE
 THE PRINTED NAME AND LICENSE NUMBER OF
 SIFANG ZHAO, P.E. PLANS/REPORTS SIGNED &
 SEALED BY A PROFESSIONAL ENGINEER SHALL
 INCLUDE EITHER THE NAME, ADDRESS AND
 LICENSE NUMBER OF THE ENGINEER OR, THE
 NAME AND LICENSE NUMBER OF THE ENGINEER
 AND THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS THROUGH WHICH THE ENGINEER IS
 PRACTICING (471.025 F.S. & 471.023 F.S.)
  
 4) 471.023 F.S.CERTIFICATE OF
 AUTHORIZATION.THE PLAN SHEETS AND THE
 CALCULATION REPORT DO NOT INCLUDE THE
 PRINTED CERTIFICATE OF AUTHORIZATION
 NUMBER (9324) FOR XCEL ENGINEERING CORP.
 THE TITLE BLOCK FOR ANY SHEET BEARING
 THE NAME OF AN ENGINEER PRACTICING UNDER
 A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ENGINEERING
 SERVICES, SHALL INCLUDE THE CERTIFICATE
 OF AUTHORIZATION NUMBER.
 ADD THE NUMBER (9324) TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]