2005-04-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
  
 1) SUBMIT A SANITARY RISER DIAGRAM
 SHOWING ALL PIPE SIZES, VENTING, POINT
 OF CONNECTION ECT. ALSO SUBMIT A WATER
 RISER DIAGRAM SHOWING ALL PIPES SIZES,
 VALVES, WATER HAMMER ARRESTORS, WHERE
 REQUIRED BY SECTION 604.9 AND POINT OF
 CONNECTION. SECTION 104.3.1.1. THESE
 RISER DIAGRAM SHALL BE IN ISOMETRIC
 FORM.
 2) DARK ROOM SINK, MORE INFORMATION IS
 REQUIRED. A DILUTION SINK MAY BE
 REQUIRED FOR CHEMICALS USED IN THIS
 PROCESS. CONTACT RODNEY COMPO,
 ENVIRONMENTAL COMPLIANCE MANAGER, (561)
 837-4074 OR E-MAIL [email protected] FOR
 DETERMINATION. SUBMIT SHEET FROM RODNEY
 COMPO WITH PLANS WHEN RESUBMITTING.
 3) ALL DEVICES, APPURTENANCES,
 APPLIANCES AND APPARATUS INTENDED TO
 SERVE SOME SPECIAL FUNCTION, SUCH AS
 STERILIZATION, DISTILLATION, PROCESSING,
 COOLING OR STORAGE OF ICE OR FOODS AND
 THAT CONNECT TO EITHER THE WATER SUPPLY
 OR DRAINAGE SYSTEM, SHALL BE PROVIDED
 AGAINST BACKFLOW, FLOODING, FOULING,
 CONTAMINATION OF THE WATER SUPPLY SYSTEM
 AND STOPPAGE OF THE DRAIN. SECTION 422.3
  
 REVIEW BY KEN STEVENS