| Plan Review Notes For Permit 05031875 |
| Permit Number |
05031875 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-04-13 00:00:00 | 1) PLEASE PROVIDE THE LOCATIONS OF | | | EMERGENCY LIGHTING FACILITIES OF ALL | | | AREAS INCLUDING THE CLASSROOMS. | | | | | | 2) PLEASE PROVIDE REASONING FOR THE | | | CLASSROOMS SHOWING NO EXIT SIGNS. | | | | | | 3) FIRE EXTINGUISHERS SHALL BE LOCATED | | | NOT TO EXCEED A 75' TRAVEL DISTANCE. | | | | | | 4) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATIONS FOR WALLS AND CEILINGS. | | | | | | 5) ALL CONSTRUCTION, ALTERATION AND | | | DEMOLITION SHALL COMPLY WITH NFPA 241. | | | | | | | | | MIKE WENNERGREN, A/CAPTAIN | | | WPBFR(561) 835-2910 |
|