2005-04-04 00:00:00******* UNSAT *******
  
 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS
 AND CORRELATE WITH A PANEL SCHEDULE TO
 BE SUBMITTED.
 PLEASE INDICATE SIZE OF PANEL AND LOAD
 ON PANEL.
 215.5,220
  
 2)NOTE: PLEASE VERIFY EXISTING RECEPTS
 SHOWN WITHIN6' OF SINKS FOR GFI
 PROTECTION.. 210.8
  
 3)NOTE: PLEASE INCLUDE CIRCUITING FOR
 EM/EXT LTS PER 700.12E.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.