| 2005-05-02 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05031875 |
| | ADD: 1411 N FLAGLER # 3900 |
| | CONT: THE WEITZ CO |
| | TEL: (561)951-2677 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENEID |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, THE |
| | HALLWAY RIGHT OF THE DOUBLE DOORS |
| | INDICATES A 1 HR RATING ONLY ON 1 SIDE |
| | OF THE HALLWAY NO RATING , NOR DOES THE |
| | WALL CONTINUE TO THE DECK ABOVE? |
| | 419.3.9.5 ALL SMOKE PARTITIONS, |
| | HORIZONTAL EXITS, AND EXIT PASSAGEWAY |
| | PARTITIONS SHALL BE CONSTRUCTED PRIOR TO |
| | THE THE CONSTRUCTION OF INTERVENING |
| | WALLS. |
| | |
| | 3) HALLWAY TO THE LEFT OF THE DOUBLE |
| | DOORS, THE CEILING IS NOT INDICATED NOR |
| | IS THE RATING OF THE DOUBLE DOORS. |
| | ?419.3.9.7 WHERE IT IS NOT POSSIBLE TO |
| | INSPECT SMOKE PARTITIONS |
| | BECAUSE OF THE FIRE TESTED MEMBRANE, |
| | FIRE-RATED ACCESS PANELS SHALL BE |
| | INSTALLED ADJACENT TO EACH SIDE OF |
| | THE SMOKE PARTITIONS AT INTERVALS |
| | NOT EXCEEDING 30 FEET (9.00 METERS) |
| | AND IN SUCH LOCATIONS AS NECESSARY |
| | TO VIEW ALL SURFACES OF THE |
| | PARTITION. |
| | |
| | 4) 704.2.1.4 CORRIDOR PARTITIONS, |
| | SMOKE STOP PARTITIONS, HORIZONTAL EXIT |
| | PART- ITIONS, EXIT ENCLOSURES, AND FIRE |
| | RATED WALLS REQUIRED TO HAVE PROTECTED |
| | OPENINGS SHALL BE EFFECTIVELY AND |
| | PERMANETLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE |
| | AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| | TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| | CEILING CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| | PROTECT ALL OPENINGS". |
| | |
| | 5) INDICATE THE LOCATION OF EXIT LIGHTS: |
| | ?1016.1.1 ILLUMINATION OF MEANS OF |
| | EGRESS SHALL BE PROVIDED IN |
| | ACCORDANCE WITH THIS SECTION FOR EVERY |
| | BUILDING AND STRUCTURE.FOR THE |
| | PURPOSES OF THIS REQUIREMENT, EXIT |
| | ACCESS SHALL INCLUDE ONLY DESIGNATED |
| | STAIRS, AISLES, CORRIDORS, RAMPS, |
| | ESCALATORS AND PASSAGEWAYS LEADING TO |
| | AN EXIT.FOR THE PURPOSES OF THIS |
| | REQUIREMENT, EXIT DISCHARGE SHALL |
| | INCLUDE ONLY DESIGNATED STAIRS, |
| | AISLES, CORRIDORS, RAMPS, ESCALATORS, |
| | WALKWAYS AND EXIT PASSAGEWAYS LEADING |
| | TO A PUBLIC WAY. |
| | |
| | 6) ?435.4.4 POSTING OF AIRBORNE |
| | RADIOACTIVITY AREAS. THE LICENSEE SHALL |
| | POST EACH AIRBORNE RADIOACTIVITY AREA |
| | WITH A CONSPICUOUS SIGN OR SIGNS |
| | BEARING THE RADIATION SYMBOL AND THE |
| | WORDS "CAUTION, AIRBORNE |
| | RADIOACTIVITY AREA" OR "DANGER, |
| | AIRBORNE RADIOACTIVITY AREA." |
| | |
| | ?435.4.5 POSTING OF AREAS OR ROOMS IN |
| | WHICH LICENSED MATERIAL IS USED OR |
| | STORED. THE LICENSEE SHALL POST EACH |
| | AREA OR ROOM IN WHICH THERE IS USED |
| | OR STORED AN AMOUNT OF LICENSED |
| | MATERIAL EXCEEDING 10 TIMES THE QUANTITY |
| | OF SUCH MATERIAL SPECIFIED IN STATE OF |
| | FLORIDA OFFICE OF RADIATION CONTROL |
| | RADIOACTIVE MATERIAL REQUIRING |
| | LABELING, MAY 2000, WHICH IS HEREIN |
| | INCORPORATED BY REFERENCE AND WHICH IS |
| | AVAILABLE FROM THE DEPARTMENT, WITH |
| | A CONSPICUOUS SIGN OR SIGNS BEARING |
| | THE RADIATION SYMBOL AND THE WORDS |
| | "CAUTION, RADIOACTIVE MATERIAL(S)" OR |
| | "DANGER, RADIOACTIVE MATERIAL(S)." |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |