Plan Review Notes
Plan Review Notes For Permit 05031875
Permit Number 05031875
Review Stop B
Sequence Number 1
Notes
Date Text
2005-05-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05031875
 ADD: 1411 N FLAGLER # 3900
 CONT: THE WEITZ CO
 TEL: (561)951-2677
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENEID
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED, THE
 HALLWAY RIGHT OF THE DOUBLE DOORS
 INDICATES A 1 HR RATING ONLY ON 1 SIDE
 OF THE HALLWAY NO RATING , NOR DOES THE
 WALL CONTINUE TO THE DECK ABOVE?
 419.3.9.5 ALL SMOKE PARTITIONS,
 HORIZONTAL EXITS, AND EXIT PASSAGEWAY
 PARTITIONS SHALL BE CONSTRUCTED PRIOR TO
 THE THE CONSTRUCTION OF INTERVENING
 WALLS.
  
 3) HALLWAY TO THE LEFT OF THE DOUBLE
 DOORS, THE CEILING IS NOT INDICATED NOR
 IS THE RATING OF THE DOUBLE DOORS.
 ?419.3.9.7 WHERE IT IS NOT POSSIBLE TO
 INSPECT SMOKE PARTITIONS
 BECAUSE OF THE FIRE TESTED MEMBRANE,
 FIRE-RATED ACCESS PANELS SHALL BE
 INSTALLED ADJACENT TO EACH SIDE OF
 THE SMOKE PARTITIONS AT INTERVALS
 NOT EXCEEDING 30 FEET (9.00 METERS)
 AND IN SUCH LOCATIONS AS NECESSARY
 TO VIEW ALL SURFACES OF THE
 PARTITION.
  
 4) 704.2.1.4 CORRIDOR PARTITIONS,
 SMOKE STOP PARTITIONS, HORIZONTAL EXIT
 PART- ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 5) INDICATE THE LOCATION OF EXIT LIGHTS:
 ?1016.1.1 ILLUMINATION OF MEANS OF
 EGRESS SHALL BE PROVIDED IN
 ACCORDANCE WITH THIS SECTION FOR EVERY
 BUILDING AND STRUCTURE.FOR THE
 PURPOSES OF THIS REQUIREMENT, EXIT
 ACCESS SHALL INCLUDE ONLY DESIGNATED
 STAIRS, AISLES, CORRIDORS, RAMPS,
 ESCALATORS AND PASSAGEWAYS LEADING TO
 AN EXIT.FOR THE PURPOSES OF THIS
 REQUIREMENT, EXIT DISCHARGE SHALL
 INCLUDE ONLY DESIGNATED STAIRS,
 AISLES, CORRIDORS, RAMPS, ESCALATORS,
 WALKWAYS AND EXIT PASSAGEWAYS LEADING
 TO A PUBLIC WAY.
  
 6) ?435.4.4 POSTING OF AIRBORNE
 RADIOACTIVITY AREAS. THE LICENSEE SHALL
 POST EACH AIRBORNE RADIOACTIVITY AREA
 WITH A CONSPICUOUS SIGN OR SIGNS
 BEARING THE RADIATION SYMBOL AND THE
 WORDS "CAUTION, AIRBORNE
 RADIOACTIVITY AREA" OR "DANGER,
 AIRBORNE RADIOACTIVITY AREA."
  
 ?435.4.5 POSTING OF AREAS OR ROOMS IN
 WHICH LICENSED MATERIAL IS USED OR
 STORED. THE LICENSEE SHALL POST EACH
 AREA OR ROOM IN WHICH THERE IS USED
 OR STORED AN AMOUNT OF LICENSED
 MATERIAL EXCEEDING 10 TIMES THE QUANTITY
 OF SUCH MATERIAL SPECIFIED IN STATE OF
 FLORIDA OFFICE OF RADIATION CONTROL
 RADIOACTIVE MATERIAL REQUIRING
 LABELING, MAY 2000, WHICH IS HEREIN
 INCORPORATED BY REFERENCE AND WHICH IS
 AVAILABLE FROM THE DEPARTMENT, WITH
 A CONSPICUOUS SIGN OR SIGNS BEARING
 THE RADIATION SYMBOL AND THE WORDS
 "CAUTION, RADIOACTIVE MATERIAL(S)" OR
 "DANGER, RADIOACTIVE MATERIAL(S)."
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  
  
  
  