| 2006-07-22 00:00:00 | *** REDLINED PLANS *** |
| | |
| | TO BE REVISED BEFORE FINAL/ C.O. |
| | |
| | 1) NOTE: PLEASE SEE DINING RM CIRUIT |
| | SHOWN AT 1000VA WHEN 1500VA MIN IS |
| | REQUIRED PER 210.52B1,210.11C1,220.16 |
| | |
| | 2) NOTE: PLEASE SEE CU CIRCUIT SHOWS |
| | 1000VA ON ONE PHASE AND 1500 VA ON THE |
| | OTHER. THIS IS NOT POSSIBLE. PLEASE |
| | ADJUST LOADS AND VA. |
| | 408.4, 240.4, ETC |
| | 106.1.2 FBC. |
| | |
| | 3) NOTE: PLEASE SEE ITEMS SHOWN AS |
| | 1-POLE/2-POLE?? |
| | |
| | 4) NOTE: PLEASE VERIFY THE LOCATION OF |
| | SD REQUIRED IN THE IMMEDICATE VICINITY |
| | OUTSIDE BEDRMS#2, AND #3. SEE NFPA-72 |
| | 11.5.1.1,11.8.3. |
| | |
| | 5) NOTE: PLEASE SEE GD OPENER SHOWS |
| | 1000VA ON LOAD CALCULATIONS, YET SHOWS |
| | 1200VA ON PANEL SCHEDULE? PLEASE |
| | CORRELATE AND ADJUST. |
| | 408.4, 106.1.2 |
| | |
| | 6) NOTE: VERIFY DEN CIRCUIT AS THIS |
| | SHOWS 15A BRKR AND #12 AWG. THIS IS OK, |
| | HOWEVER IF SHOWN THIS WAY THEN THIS WILL |
| | BE VERIFIED. |
| | |
| | 7) NOTE: PLEASE SEE THE DISHPOSAL AND |
| | DISHWASHER IS ONLY TO VERIFY IF THESE |
| | ARE BOTH ON SEPARATE RECEPTS. IF BOTH |
| | ARE FED TO ONE RECEPTS, THEN THIS RECEPT |
| | MUST BE FED FROM A TWO POLE BREAKER. |
| | PLEASE ONLY REVISED PANEL SCHEDULE FOR |
| | 2-POLE BRKR IF INDEED ONE DEVICE/RECEPT |
| | FEEDS BOTH. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW BEFORE FINAL CO. IF THERE ARE ANY |
| | QUESTIONS, PLEASE DO NOT HESITATE TO |
| | CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |